Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2014 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 07/24/2014 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/18/2014 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/18/2014 | BUILDING - FINAL | Denied | ITEMS ON LIST HAVE NOT BEEN CORRECT, RE FEE WILL BE POSTED FOR NEXT INSPECTION | |
| 07/02/2014 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/02/2014 | BUILDING - FINAL | Denied | 1. LB FROM METER BASE TO DISCONECT LOOSE 2. LABELS MISSING AT SERVICE 3. SERVICE PANEL RATING NOT TO PRINT 4. INVERTERS TO BE ANCHOR TO WALL AT THE BOTTOM 5. BREAKER IN COMBINER ON LOAD CENTER NOT TO PRINT 6. GROUNDING ELECTRODE IN INVERTER TO BE PUT ON BOND BUSHING 7. NEUTRALS TO INVERTER PHASED NOT TO CODE 8. PIPE STANDS MISSING ADHESIVE & MINIS NOT TO CODE FOR STRAPPING ON ROOF 9. PANELS & RAIL LOOSE ON ROOF |
|
| 06/30/2014 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* |