Permit: T14CM02611

Parcel: 136327930

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
07/31/2014 BUILDING - FINAL Approved IVRS - Inspection :*
07/24/2014 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/18/2014 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/18/2014 BUILDING - FINAL Denied ITEMS ON LIST HAVE NOT BEEN CORRECT, RE FEE WILL BE POSTED FOR NEXT INSPECTION
07/02/2014 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/02/2014 BUILDING - FINAL Denied 1. LB FROM METER BASE TO DISCONECT LOOSE
2. LABELS MISSING AT SERVICE
3. SERVICE PANEL RATING NOT TO PRINT
4. INVERTERS TO BE ANCHOR TO WALL AT THE BOTTOM
5. BREAKER IN COMBINER ON LOAD CENTER NOT TO PRINT
6. GROUNDING ELECTRODE IN INVERTER TO BE PUT ON BOND BUSHING
7. NEUTRALS TO INVERTER PHASED NOT TO CODE
8. PIPE STANDS MISSING ADHESIVE & MINIS NOT TO CODE FOR STRAPPING ON ROOF
9. PANELS & RAIL LOOSE ON ROOF
06/30/2014 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*