Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T14CM02579
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/18/2014 | FIRE - FINAL | Approved | They remove the damper and fire rated the wall | |
07/03/2014 | FIRE - FINAL | Denied | 1. Seal around damper holes in wall. 2. Add smoke gasket on door 3. Need to add smoke duct detection within 5' from fire/smoke damper in hallway per IBC 715.3.2.1 2000ED & IBC 717.3.3.2 2012ED. |
|
07/01/2014 | FIRE - FINAL | Denied | 1. Fire doors did not release upon activation. 2. Fire damper did not close. |