Permit: T14CM02573

Parcel: 12810079B

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T14CM02573

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/25/2014 FIRE - FINAL Approved
07/23/2014 FIRE - FINAL Denied 1. Get hood final first
2. Panic hardware on 2nd exit door needed IFC1008.1.10 NOTE: remove thumb style dead bolt lock from door when installing panic hardware.
3. IFC1008.1.9.3 Install (over double doors) readily visible durable sign on the egress side on or adjacent to the door stating the following: "THIS DOOR TO REMAIN UNLOCKED WHEN BUILING IS OCCUPIED". The sign shall be in letters 1-inch high on a contrasting background.
4. Post Occ. Load sign by main front door, per approved plans load is "94"
07/15/2014 FIRE - FINAL Denied 1. Correct sprinkler coverage front of the hood and office area.
2. 05390 Fire-Kitchen Exg Hood Final has been added to your inspection card.
3. Need all subs call in for there final before calling in your final.
07/03/2014 FIRE - FINAL Not ready for Inspection Just call in to ask questions about where to install pull station I did approved to install pull station 10 feet way in kitchen next to double sink on the 6 inch wall

Correct sprinkler coverage in the bar area