Permit: T14CM02403

Parcel: 11516023B

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
06/18/2014 FIRE - FINAL Approved
06/16/2014 FIRE - FINAL Denied 1. Need annual sprinkler and 5 year check valve inspections.
2. Need to correct sprinkler coverage in office # 08 cannot have a quick response and standard head types in the same room.
3. Add suite numbers on front and rear doors 3 inch size
4. Install exit signs over all egress door in the warehouse (doors #13A & 13B as stated in plans) and in west office over egress door (#9B as stated in plans).
5. Repair or replace back up lighting in office and warehouse
6. Remove sliding bolt lock and padlock locking device on double doors to warehouse.