Permit: T14CM02389

Parcel: 125070720


Addresses:

2515 E 4TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/19/2014 PLUMBING - FINAL Approved
05/16/2014 PLUMBING - FINAL Denied NO ACCESS TO WATER HEATER.
05/05/2014 PLUMBING - FINAL Not ready for Inspection 1. Water heater installed without inspection. T&P relief drain to be gravity type drain, flex not permitted. Kinks not allowed. Vent connector to have three machine screws at each joint. Gas flex too long. Require an approved valve. Require straps on roof. Seal the roof jack. Gas pressure test to be on at the time of the inspection. OK to connect to existing. Call SW Gas when operating their valve- they want to test the regulator.