Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2014 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/03/2014 | MECHANICAL - FINAL | Partial Approval | THIS IS NOT ROOFTOP REPLACMENT THIS IS A NEW INSTALL & REQUIRES A STRUCTRUAL DRAWINGS APPROVED BY C.O.T | |
| 07/22/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/22/2014 | MECHANICAL - FINAL | Denied | PROVIDE REQUIRED PLAN COMPLETE ALL NOTES CORRECTION FAILER TO COMPLY MAY RESULT IN RE INSPECTION FEES | |
| 07/17/2014 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/10/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/10/2014 | MECHANICAL - FINAL | Denied | ELEC CONDUIT NOT LONG ENOUGH & NOT TERMINATED THROUGH THE ROOF JACK PROPERLY PAINT EXPOSED PVC WITH LATEX PAINT. COVER EXPOSED SIDE OF CANVAS CONNECTOR. CAP OFF THE ABANDONED FURNACE VENT IN CLOSET & USE METAL FOR CAPPING. WRONG DESCRIPTION. NOT AN AC REPLACEMENT. PROVIDE THE REQUIRED DRAWING FOR NEW AC ON ROOFTOP |