Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/20/2015 | PLUMBING - PROGRESS | Approved | PER BLDG FINAL | |
| 01/14/2015 | PLUMBING - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/14/2015 | PLUMBING - PROGRESS | Denied | COURTESY UNSCH INSP FOR ANDREWC PLEASE INSTALL HB VACUUM BREAKER AT THIS TIME FOR PUBLIC SAFETY OR REMOVE BIB. REMOVE ADHESIVE TAPE FROM PET PER MII PRIOR TO COVERING REDLINE SITE PLAN TO SHOW CHANGE |
|
| 09/19/2014 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 09/19/2014 | PLUMBING - PROGRESS | Not ready for Inspection | CORRECT SLOPE OF PLIT SINK DRAIN, SECURE FOAM WRAP | |
| 09/05/2014 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 09/05/2014 | PLUMBING - PROGRESS | Not ready for Inspection | NOTE: SANITARY (BLACK) SYSTEM REQUIRES A LAUNDRY CONNECTION. OK TO WET VENT OVER WC. RISER ADDED TO GREY SYSTEM ONLY. ALL 2" RISERS IN TOILET ROOMS ARE CONNECTED TO GREY SYSTEM. LB 1410. APPROVED PLAN SHALL BE ON SITE (WRONG PLAN LEFT FOR INSPECTION). | |
| 09/03/2014 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 09/03/2014 | PLUMBING - PROGRESS | Not ready for Inspection | NOT INSTALLED PER PLAN. PROVIDE WASHING MACHINE DRAIN (BLK). PROVIDE 3" CLEANOUTS AS SPECIFIED AT EACH WC. |