Inspection History: FIRE - FINAL
Permit Number - T14CM02300
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2015 | FIRE - FINAL | Approved | ||
| 11/25/2015 | FIRE - FINAL | Partial Approval | Temporary C of O approved for services and moving in furniture, to get a fire final the following shall be completed: Fire Alarm final Fire sprinkler final Need to install emergency lights outside each egress door per approved plans Install F.D. key boxes 5 feet Repair or replace exit sign over east assembly room door emergency lighting failed. Address numbers posted on buildings 15 inch size handout given |
|
| 08/03/2015 | FIRE - FINAL | Denied | Was told they will need F.D. key system on all gates that accesses the property and will need F.D. key box for the riser room and sign the riser room door "RISER ROOM" red lettering white background. Also advised them they will need to sign over the fire department connection with a sign "FDC" red lettering white reflected background high on wall to be seen from road. |