Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2015 | FIRE - ALARM FINAL | Approved | ||
| 11/25/2015 | FIRE - ALARM FINAL | Denied | 1. Alarm inspection approved pending acceptance of alarm plans by the Fire Code Administrator. 2. Need speakers installed in the following areas: South and North corridors, both crying rooms. 3. Move the strobe from behind the door north crying room. |
|
| 08/03/2015 | FIRE - ALARM FINAL | Correction Required | After reviewing the building plans for the occupant load on pg A0.1 (T14CM02300) the total is 2131 therefore a voice system shall be install and not horns/strobes IFC 907.2.1.1. Alarm plans that are currently approved are horns/strobes for occupant load of 998 (T15BU00651). |