Permit: T14CM02300

Parcel: 13817047B


Addresses:

301 E LOS REALES RD

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
12/10/2015 FIRE - ALARM FINAL Approved
11/25/2015 FIRE - ALARM FINAL Denied 1. Alarm inspection approved pending acceptance of alarm plans by the Fire Code Administrator.
2. Need speakers installed in the following areas: South and North corridors, both crying rooms.
3. Move the strobe from behind the door north crying room.
08/03/2015 FIRE - ALARM FINAL Correction Required After reviewing the building plans for the occupant load on pg A0.1 (T14CM02300) the total is 2131 therefore a voice system shall be install and not horns/strobes IFC 907.2.1.1. Alarm plans that are currently approved are horns/strobes for occupant load of 998 (T15BU00651).