Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/02/2014 | FIRE - FINAL | Approved | All corrections completed | |
| 05/20/2014 | FIRE - FINAL | Denied | 1. IFC 506.1 Need fire department key system installed on entrance gate 2. IFC 906.2 Fire extinguisher shall be installed in the following areas: 1. Apartment (1) 1-A:10BC 2. Business office (1) 2A:10BC 3. Garage (1) 2A:10BC Mount all fire extin. on walls 3. IFC 907.2.11.2 Replace old out dated smoke alarm with a new hard wired battery backup smoke detector, also install one in the loft area above the kitchen. 4. IFC 1008.1.9 & 1008.1.9.4 2nd floor egress door to roof shall have a thumb style turn lock cannot have a double cylinder keyed dead bolt lock, also remove slide bolt lock on door. 5. IFC 605.1 Replace missing cover plates in the garage single cover plate mounted on ceiling, replace missing 3" elbow cover plate in electrical panel room. Label panels to what they serve such as apartment, garage ect. |