Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/15/2014 |
PLUMBING - FINAL |
|
Approved |
|
| 05/07/2014 |
PLUMBING - FINAL |
|
Not ready for Inspection |
1. Comply with all of the corrections from 04/24/14 You may backfill after cleaning out the trench. |
| 04/24/2014 |
PLUMBING - FINAL |
|
Not ready for Inspection |
1. Plan not accurate. Plan not complete. Include total BTUs contributed by existing piping. Existing line does ot hold pressure. Provide access to existing line and all appliances served. Where is the bond between the gas and the water. Plugged tees are not permitted unless shown on the plan as future. Remove all aggregates from trench before backfilling. Only clean fill to be used for 6" around pipe. Note: over 15,000 fires a year are started by lint. |