Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2014 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* COMPLETE ITEMS FROM 4/21 | |
| 08/18/2014 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/18/2014 | ELECTRIC - FINAL | Partial Approval | SUBJECT TO NOTES FOR UPGRADE | |
| 04/21/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/21/2014 | ELECTRIC - FINAL | Denied | - VERIFY NEW PANEL UPGRADE WAS INSPECTED AND PERMITTED, OR ADD TO PERMIT - SCHEDULE POWER-KILL WITH TEP - NOTE: PANEL IS ENERGIZED - MAX 15 AMP BREAKERS ON #14 WIRE - VERIFY GAS/WATER BONDS - GROUND ALL RECEPTACLES AND PROVIDE TWO-HOLE TYPE IF REQUIRED - PROVIDE SMOKE ALARMS IN ALL BEDROOMS - 200 AMP PANEL REQUIRES 2/0 SERVICE CONDUCTORS |