Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2014 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/30/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/30/2014 | ELECTRIC - FINAL | Denied | - ROMEX TO SHED NOT TO CODE. CANNOT OPEN PANEL COVER SAFELY. REMOVE OR WIRE TO CODE - WHITE FEEDER WIRE TO SUBPANEL USED AS HOT WIRE SHOULD BE BLACK OR ADD MORE BLACK TAPE. INSTALL BOND BUSHING ON NIPPLE - 2 GROUND RODS REQUIRED 6' APART, BOND WATER & GAS PIPING - PLUG UNUSED OPENINGS IN SUBPANEL |