Inspection History: FIRE - FINAL

Permit Number - T14CM02182

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/13/2015 FIRE - FINAL Approved
04/07/2015 FIRE - FINAL Denied 1. Repair exit sign over front exit door back up lighting failed
2. Change sign over front entrance door to state what is on approved plans PG A.0 "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED"
3. Need fire extinguishers mounted one for every 1500 sq. feet of building and travel distance of 75 feet.
4. Need to replace worn out address numbers handout given.