Permit: T14CM02182

Parcel: 10604252D

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T14CM02182

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/04/2015 BUILDING - FINAL Approved IVRS - Inspection :*
05/01/2015 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
04/30/2015 BUILDING - FINAL Not ready for Inspection SEE NOTES FROM 04/15/15
04/22/2015 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
04/22/2015 BUILDING - FINAL Not ready for Inspection STILL NEED TO CORRECT WAG D (?) TERMINATION AND ADDRESS MATERIAL CHANGES. HARD CAP ABANDON VTR. UV PW (?) ON 10 MIL PIPE WRAP
04/15/2015 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
04/15/2015 BUILDING - FINAL Not ready for Inspection CORRECT OR REMOVE SUITE NUMBER. PROVIDE ROOF ACCESS. CALL FOR AND HAVE APPROVED ALL INTERMEDIATE INSPECTIONS. WATER HEATER IS NOT PER PLAN. STORAGE TANK REQUIRED. AN EXPANSION DEVICE AND VACUUM RELIEF VALVE. ALSO, MOVE RELIEF DRAIN PIPE TO ALLOW CO ACCESS. INSTALL HOSE BIB VACUUM BREAKERS (BOTH). WAGD TERMINATION IS NOT PER PLAN. INSTALL PER PLAN OR REVISE. 10' CLEAR IS REQUIRED. ALSO, SCREEN. CORRECT SLOPE OF CONDENSATE AT WALL PENETRATION. PLAN SPECIFIES COPPER FOR CONDENSATE PIPING. PROVIDE UV PROTECTION ON ALL PLUMBING AND MECHANICAL PIPING EXPOSED TO SUN. PLAN SPECIFIES A METAL JACKET ON HYDRONIC PIPING.
****IMPORTANT!! CHILLER MAKEUP WATER DIRECT CONNECTION REQUIRES HIGH HAZARD BACKFLOW PROTECTION W/ TEST REPORT. NOT INSTALLED PER PLAN****