Permit: T14CM02068

Parcel: 129022450


Addresses:

2634 E DEVON ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
04/29/2014 BUILDING - FINAL Approved IVRS - Inspection :*
04/28/2014 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/28/2014 BUILDING - FINAL Denied **AS PER LAST INSPECTION ON 04/25/14 NOTES:**
- ARC FAULT NOT WORKING UNDER TEST AT OUTLET
- WIRING TO DWELLING NOT PER PLAN. REVISE PLAN, PERMIT FOR NEW WIRING OR OBTAIN A LETTER SIGNED BY A LICENSED ELECTRICAL CONTR STATING ALL WIRING IS TO CODE & WORKING PROPERLY
04/25/2014 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/25/2014 BUILDING - FINAL Denied 1. MISSING SMOKE ALARM PER PLAN IN HALLWAY
2. ARC FAULT PROTECT BEDROOM CIRCUIT PER PLAN
3. 40 AMP WHITE HOT LEAD TO BE RED OR BLACK (TAPE OK)
4. LABEL CIRCUIT PANEL. IT APPEARS, DUE TO NEW WIRING TO PANEL, ENTIRE HOME HAS BEEN REWIRED
5. BY CODE, DOUBLE LAV REQUIRES GFCI OUTLET IN CENTER OR 1 ON EACH END
6. HAMMER ARRESTORS IN LAUNDRY
04/23/2014 BUILDING - FINAL Denied FINISH DRYWALL IN LAUNDRY ROOM
04/23/2014 BUILDING - FINAL Denied FINISH DRYWALL IN LAUNDRY ROOM
04/16/2014 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/16/2014 BUILDING - FINAL Denied REMOVE SHEETROCK TO SHOW INTERMEDIATE PLUMBING AND ELECTRICAL