Permit: T14CM01996

Parcel: 127022690


Addresses:

5324 E 1ST ST 12

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
01/15/2016 FIRE - ALARM FINAL Approved
04/23/2015 FIRE - ALARM FINAL Partial Approval PHASE #1 partial approval
The following was completed and passed for Phase #1:
1. Duct smokes
2. Smoke above NAC panel
3. Pull stations
4. Horns and strobes
5. Dated batteries in NAC
6. NAC electrical panel labeled
The following will need to be done before phase #2 final will be given:
1. Need lock out installed on breaker for the alarm NAC
2. Need lock out installed on breaker for the fire Bell