Permit: T14CM01996

Parcel: 127022690


Addresses:

5324 E 1ST ST 12

Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Date Description Inspector Results Comments
03/24/2015 FIRE SPKLR - UG, PIPING, HYDRO Approved
03/10/2015 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval Underground is going to be installed in 2 parts due to not having open tranches;
First part inspected 4" CPVC from riser base to the sidewalk, all mag lugs in place and wrapped with plastic and all tracer wiring in place depth is over 36". OKAY to bury but still needs 200 PSI for 2 hours and flush.