Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2016 | PLUMBING - FINAL | Approved | ||
| 01/25/2016 | PLUMBING - FINAL | Denied | IVRS - Inspection :23No Description.| 99946 * |
|
| 01/22/2016 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/28/2015 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/27/2015 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* | |
| 04/24/2015 | PLUMBING - FINAL | Partial Approval | INSTALL CHECK VALVE UP STREAM OF EXP TANK AS SHOWN. CORRECT SPLASHING. CORRECT MS CONN. REMOVE TRAP COVERED (??) AT FS. STEAM OVEN APPEARS TO REQUIRE BACKFLOW PROTECTION. ICE MAKER NOT INSTALLED | |
| 04/22/2015 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/22/2015 | PLUMBING - FINAL | Not ready for Inspection | EXHAUST FAN TIMERS, ELECTRICAL CONNECTIONS. UV PROTECTION. PROVIDE WATER CONNECTION FOR SOAP DISPENSER. CHECK VALVE AT WATER HEATER, PER DETAIL. SUPPORT PIPING AT DW. WATER TEST FIXTURES FOR SPLASHING |