Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T14CM01963
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/15/2014 | FIRE SPKLR - FINAL | Approved | ||
07/14/2014 | FIRE SPKLR - FINAL | Denied | Check all up right coverage for proper spacing and a max of 12 inches from deck: 1. Correct sprinkler coverage some upright heads are more than 12" inches from deck. 2. Correct sprinkler coverage front entrance pocket space lacking upright coverage. |