Permit: T14CM01928

Parcel: 14024053A


Addresses:

6250 S DEL MORAL BL

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
07/30/2014 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
07/29/2014 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
07/25/2014 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/25/2014 ELECTRIC - SERVICE UPGRADE Denied 1. BOND HUBS 2 1/2"
2. BOND BUSHINGS AT 2" TERMINATIONS IN CT 2" EMT CONNECTORS NOT SEATED FLAT (TIGHT) AGAINS CTCAN
3. INSTALL FUSES R-PINS IN DISC SW'S
4. GROUND ELECTRODE CONDUCTOR PER 250.66 NEC. GROUND RODS TO BE FLUSH WITH GRADE