Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2014 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/29/2014 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 07/25/2014 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/25/2014 | ELECTRIC - SERVICE UPGRADE | Denied | 1. BOND HUBS 2 1/2" 2. BOND BUSHINGS AT 2" TERMINATIONS IN CT 2" EMT CONNECTORS NOT SEATED FLAT (TIGHT) AGAINS CTCAN 3. INSTALL FUSES R-PINS IN DISC SW'S 4. GROUND ELECTRODE CONDUCTOR PER 250.66 NEC. GROUND RODS TO BE FLUSH WITH GRADE |