Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/28/2014 | FIRE - FINAL | Approved | Address numbers posted Tested gate operations: Turned power off gate open and stayed open until power was turned back on Tested by-pass switch passed Tested for low battery gate stayed open |
|
| 05/12/2014 | FIRE - FINAL | Denied | 1. IFC 505.1 Address numbers shall be posted on wall 12 inch size per handout given. 2. IFC503.6.1 Electric Gate: Electric gates that use electric to automatically open or unlock shall have a manual override system. Manual override controls shall be located on the entrance side of gate, or when power failed the gate(s) shall open and stay open until power is restored for normal operations. 3. Need to call in permit #T14CM01925 for all finals Phone # 740-6970 day before inspection date and before 3:15 P.M. |