Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
Permit Number - T14CM01837
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/03/2014 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
01/05/2006 | ELECTRIC - RECONNECT | Denied | COMMENTS TRANFERRED FROM T06EL00010 #1 SERVICE - IMPROPER SERVICE GROUNDING, IMPROPER WIRING METHODS, OPEN WIRING, MULTIPLE LUGGING, UNATTACHED WIRING SE CABLE GOING INTO BLDG W/O PROTECTION, IMPROPER OVER CURRENT PROTECTION. #2 OUTSIDE COMPRESSOR - OPEN WIRING, OPEN RACEWAYS, MISSING COVERS, NORTH WALL OUTSIDE UNSUPPORTED WIRING & CONDUITS, OUTSIDE OPEN SPLICES TO LIGHTING. #3 LIFT AREA - NON WEATHERPROOF WIRING DEVICES, OUTDOOR PANEL ON WALL NOT RATED FOR OUTSIDE. #4 OUTDOOR SPRAY BOOTHS - OUTSIDE WIRING NOT WEATHERPROOF REMOVE OR CORRECT. #5 ALL OUTSIDE LIGHTING TO BE WEATHERPROOF & LISTED FOR AREA #6 EAST AREA OUTSIDE COMPRESSORS TO BE WIRED CORRECTLY #7 ALL INSIDE LIGHTING TO BE WIRED CORRECTLY NO OPEN SPLICING - USE LIGHTING AT PROPER HEIGHTS - 12' #8 REMOVE ROMEX IN SHOP AREA TOO MANY ELECTRICAL VIOLATIONS - OBTAIN SERVICES OF ELECTRICAL CONTRACTOR TO CORRECT ELECTRICAL VIOLATIONS & RECALL FOR INSPECTION. |