Permit: T14CM01766

Parcel: 110113620

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T14CM01766

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/24/2014 FIRE - FINAL Approved 1st inspection at 9:30 AM theater 4 and 6 emergency lighting failed after 5 minutes of operations after leaving emergency lights on for 1 hours all theaters passed but # 4 and 6.
Emergency lighting failed over front lobby doors batteries not plugged in
Found two painted or taped heads in theater #3 along both walls.
2nd inspection at 3:30 PM new batteries installed for theaters # 4 & 6 this time they work for 1 hour and the front lobby worked also. Tape on sprinkler heads removed.
09/17/2014 FIRE - FINAL Partial Approval TEMP C OF O OKAY FOR TRAINING ONLY NO PUBLIC OR SALES
To get finals the following shall be done:
Same as last inspection on 09.16.2014
Need to repair or replace inspector test valve
Lock outs on breakers to FACP and Booster panel
Repair or replace flow switch
09/16/2014 FIRE - FINAL Denied Theater # 1
Painted head in the center of theater possible painted or dirty heads in other areas
By screen sprinkler heads block by screen not allowing for the head to properly form its spray pattern need to correct sprinkler coverage
Theater #2
By screen sprinkler heads block by screen not allowing for the head to properly form its spray pattern need to correct sprinkler coverage
4 sprinkler heads on eastside of room have taped sprinkler heads
Theater #3
By screen sprinkler heads block by screen not allowing for the sprinkler heads to properly form its spray pattern need to correct sprinkler coverage
Theater #4
By screen sprinkler heads block by screen not allowing for the sprinkler head to properly form its spray pattern need to correct sprinkler coverage
Stairwell to projector room sprinkler head on ground floor head painted
Theater #5
By screen sprinkler heads block by screen not allowing for the sprinkler head to properly form its spray pattern need to correct sprinkler coverage
Theater #6
By screen sprinkler heads block by screen not allowing for the sprinkler head to properly form its spray pattern need to correct sprinkler coverage
While inspecting the sprinkler coverage I notice over 30 sprinkler heads with blue paint spray on them therefore you are order to have a completely inspect all fire sprinkler heads for paint if they are painted you will need to change them.
Will need to replace all missing escutcheons on all sprinkler heads
Need to have alarm sub to call in there final
Need to have Hood sub call in there final
Need to have sprinkler call in there final again
09/04/2014 FIRE - FINAL Denied Need to add EM lighting over steps to rear exits in each movie theater, EM lighting to all aisles to egress ways.