Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2014 | FIRE - ALARM FINAL | Approved | ||
| 09/17/2014 | FIRE - ALARM FINAL | Partial Approval | Need lock outs on breakers for the FACP and the Booster Need to repair or replace flow switch |
|
| 09/16/2014 | FIRE - ALARM FINAL | Denied | Need all duct to shut down and report to panel Need sound system to shut down when alarm actives |