09/24/2014 FIRE SPKLR - FINAL Approved
09/17/2014 FIRE SPKLR - FINAL Partial Approval same as last inspection but need to repair or replace flow switch
Need to repair or replace inspectors test valve
09/16/2014 FIRE SPKLR - FINAL Denied Theater # 1
Painted head in the center of theater possible painted or dirty heads in other areas
By screen sprinkler heads block by screen not allowing for the head to properly form its spray pattern need to correct sprinkler coverage
Theater #2
By screen sprinkler heads block by screen not allowing for the head to properly form its spray pattern need to correct sprinkler coverage
4 sprinkler heads on eastside of room have taped sprinkler heads
Theater #3
By screen sprinkler heads block by screen not allowing for the sprinkler heads to properly form its spray pattern need to correct sprinkler coverage
Theater #4
By screen sprinkler heads block by screen not allowing for the sprinkler head to properly form its spray pattern need to correct sprinkler coverage
Stairwell to projector room sprinkler head on ground floor head painted
Theater #5
By screen sprinkler heads block by screen not allowing for the sprinkler head to properly form its spray pattern need to correct sprinkler coverage
Theater #6
By screen sprinkler heads block by screen not allowing for the sprinkler head to properly form its spray pattern need to correct sprinkler coverage
While inspecting the sprinkler coverage I notice over 30 sprinkler heads with blue paint spray on them therefore you are order to have a completely inspect all fire sprinkler heads for paint if they are painted you will need to change them.
Will need to replace all missing escutcheons on all sprinkler heads