Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/19/2014 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 05/13/2014 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/13/2014 | BUILDING - FINAL | Denied | 1. BOND BUSHING FOR GROUNDING ELECTRODE MISSING AT A/C DISCONNECT, METER BASE, & COMBINER 2. GROUNDING ELECTRODE FROM COMBINER TO INVERTER 1 & 2 NOT TO PRINT 3. J-BOX RACEWAY TO BE STRAPPED WITHIN 3' 4. EMT PIPE STANDS MISSING ADHESIVE |