Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/02/2014 | ELECTRIC - RECONNECT | Approved | PER ELEC FINAL | |
| 04/02/2014 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/02/2014 | ELECTRIC - RECONNECT | Denied | 1. MAIN BREAKER TO BE CONNECTED & BOND BUSHING MISSING 2. PANEL SCHEDULE TO BE ON DEADFRONT 3. DEADFRONT MISSING SCREW 4. SERVICE PANEL MISSING 1" K.0 SEAL 5. WIRES AT CARPORT TO BE CAPPED-OFF 6. GROUNDS & NEUTRALS TO BE SEPARATED AT SUBPANEL & SCREWS TO HOLD DEADFRONT MISSING 7. LIGHT FIXTURES THROUGHOUT HOUSE J-BOXES WIRES TO BE CAPPED-OFF & SMOKE DETECTORS MISSING 8. WATER HEATER WIRES TO BE INSTALLED & FURNACE MISSING VENT |
|
| 04/01/2014 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/01/2014 | ELECTRIC - RECONNECT | Denied | 9:20 - NO ACCESS TO SITE | |
| 03/24/2014 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/24/2014 | ELECTRIC - RECONNECT | Denied | WRONG NUMBER - NO ACCESS TO SITE |