Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/10/2014 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/03/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/03/2014 | ELECTRIC - FINAL | Denied | - APPROVED PLANS ON SITE - OBTAIN LETTER FROM LICENSED ELECTRICAL CONTR STATING HE HAS CHECKED OUT THE ENTIRE ELECTRICAL SYSTEM AND ALL IS TO CODE PER 2012 IRC - ARC FAULT CKT BREAKERS, TAMPER RESISTANT RECEPTACLES AS PER 2012 IRC - IN LIEU OF LETTER FROM LICENSED CONTR, YOU CAN REMOVE DEVICES & DRY WALL FOR INSPECTION OF WIRING |
|
| 03/21/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/21/2014 | ELECTRIC - FINAL | Denied | 1. ADD SERVICE UPGRAGE TO THE PERMIT OR OBTAIN SEPARATE PERMIT 2. 2 GROUND RODS REQUIRED 6' APART, HOMEMADE RISER CONDUIT BRACE NOT APPROVED, USE LISTED BRACE. BOND WATER/GAS PIPING 3. RE-WIRING (NEW) OF HOUSE REQUIRES APPROVED PLANS/PERMIT 4. ROOF NOT COMPLETE IN CARPORT |