Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/20/2014 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/19/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/19/2014 | ELECTRIC - FINAL | Denied | 1. PANEL NOT GROUNDED - VANDALISM 2. WHITE HOT LEADS TO BE RED OR BLACK (TAPE OK) 3. GROUND WATER HEATER 4. RELOCATE SMOKE ALARMS PER SPECS, NOT WITHIN 36" FORCED AIR REGISTER ON WALL 6"-12" FROM CEILING |