Permit: T14CM01364

Parcel: 12112301A


Addresses:

5246 E LEE ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/12/2014 PLUMBING - FINAL Approved IVRS - Inspection :*
03/11/2014 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
03/11/2014 PLUMBING - FINAL Denied - CORRECT DAMAGED/MISSING ELECTRICAL GROUND WIRE AT MAIN PANEL
- CORRECT WATER HEATER VENT & RELIEF VALVE. DAMAGED, TOUCH (?) WOOD, NOT SECURED, DRIPPING
- CORRECT PIPE SIZING AT FIRST TEE. FOLLOW PLANS
- PROVIDE 1" CLEAR AT FURNACE VENT THRU ROOF