Permit: T14CM01316

Parcel: 127035470


Addresses:

620 N CRAYCROFT RD


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T14CM01316

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/18/2014 FIRE - ALARM FINAL Approved
07/14/2014 FIRE - ALARM FINAL Denied 1. Need to add duct detectors to alarm system.
2. Need to add all smoke/fire dampers to alarm system
3. Need to fire caulk all boxes for strobes/horns, eletrical outlet boxes, switch boxes, communication's boxes and holes in walls that are located in the fire rated corridor.
4. Needs as built bubble areas where changings were made on plans and show a new matrix schedule on plans.
5. Check all fire/smoke dampers for proper caulking fond holes through walls.
6. If installing access-controlled devices on egress doors on 1st and 2nd floor from the lobbies to the 2nd exits on each floor, than both door devices will need to be added on the alarm system so that in alarm condition all egress doors with access-controlled device are by-pass and anybody can open the doors without any special knowledge or effort. IFC 1008.1.9.8
07/10/2014 FIRE - ALARM FINAL Denied Need fire alarm company to call in there permit.
07/01/2014 FIRE - ALARM FINAL Not ready for Inspection