Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/28/2015 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 08/28/2015 |
ELECTRIC - FINAL |
|
Partial Approval |
GROUNDING AND SEPARATE SOV |
| 08/25/2015 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 08/25/2015 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
DE-RATE CONDUCTORS PER NEC 310.15 (RUN ONE PAIR IN A SEPARATE RACEWAY). REPLACE DAMAGED J-BOX. SECURE RACEWAYS. PROTECT/ISOLATE FLEX FROM SHARP METAL. CONCRETE OR OTHER SOLID PAN REQUIRED |