Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2014 | FIRE - FINAL | Approved | ||
| 07/07/2014 | FIRE - FINAL | Denied | NOT APPROVED 1. Correct sprinkler coverage on top of stairs to mezzanine under exit sign spray pettern blocked by concrete. 2. Need Occ Load sign posted by front main entrance 49 OCC 3. Need fire extin. 1 for every 1500 sq. feet of building 2A-10BC. 1 for mezzanine and 1 for main floor. |