Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T14CM01235
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/08/2015 | FIRE - FINAL | Approved | ||
04/02/2015 | FIRE - FINAL | Denied | 1. Kitchen hall way exit to outside need the gate installed exiting out of the bricked storage patio area, gate will need panic hardware 2. Address numbers posted on sign at front entrance driveway 12" inch size handout given. 3. Paint address numbers on building they faded 4. Post Occupant load sign by main entrance, the following shall be on the sign: "OCCUPANT LOAD 319 Address: 6608 S. Tucson Bl." |
|
03/18/2015 | FIRE - FINAL | Denied | Same as last inspection and the following: 1. Check sprinkler coverage on floor area northeast side of stage spacing not correct. 2. Sprinkler head was painted and someone tried to clean it but paint still on copper part of sprinkler cap. 3. Check sprinkler coverage in storage closet dead space area 4' x 2' shadow |
|
03/13/2015 | FIRE - FINAL | Denied | 1.Still need to finish sprinkler work. 2.Need address numbers near street sign. |