Permit: T14CM01144

Parcel: 10714257E


Addresses:

16 W GRANT RD


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T14CM01144

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/19/2015 FIRE SPKLR - FINAL Approved
03/04/2015 FIRE SPKLR - FINAL Denied 1. Sprinkler inspections & 5 year check valve inspections are pass due need reports for all 4 risers.
2. Sprinkler escutcheons are not fitting correctly need tight fit to the ceiling no openings aloud.
3. PIV (post indicator valve) not working properly when shut down water leaks by, need to repair or replace PIV.
4. Flow switch for fire bell not work wiring pulled out and there is no WMG (water motor gong) need this repaired.
5. Need a fire alarm monitoring system install to the sprinkler system.
6. Taped upright sprinkler heads in the stock and one painted head in the bathroom, need to correct.