Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T14CM01014
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/13/2016 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
10/05/2016 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
10/05/2016 | PLUMBING - FINAL | Not ready for Inspection | 1-lav sinks too high, not to exceed 34" 2-lav mixing valves missing 3-hammer arrestors missing 4-T&P not properly terminated or per plans 5-well panel missing breaker or blank 6-A/C linesets not coated for UV protection, no tapes allowed 7-provide sterilization report 8-provide air balance report |