Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2014 | FIRE - FINAL | Approved | ||
| 05/14/2014 | FIRE - FINAL | Denied | 1. Need two fire extinguishers installed 2A 10BC type travel distance to them can't be more than 75 feet. 2. Need emergency battery backup lights by egress doors, hallway by bathrooms and dining room. |