Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2019 | FIRE - FINAL | Approved | ||
| 11/13/2019 | FIRE - FINAL | Partial Approval | APPROVED TO OBTAIN TCO FOR TRAINING ONLY. STILL NEEDS A SPRINKLER FINAL INSPECTION. | |
| 11/12/2019 | FIRE - FINAL | Partial Approval | -verify sprink final items -address numbers -FACP sign -FDC sign -add one more class K extinguisher -keys in knox box |
|
| 11/04/2019 | FIRE - FINAL | Denied | 1. Install electric bell. 2. Need address numbers. 3. Comlete CO2 test. 4. Install FDC and Knox Cap. 5. Add FDC and FACP signs. 6. Put keys in knox box. 7. Obtain Places of Assembly Permit. |