Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T14CM00783

Parcel: 13103224R


Addresses:

5180 E 22ND ST A


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T14CM00783

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/30/2015 FIRE - FINAL Approved Added 1A:10B:C type extinguishers in each unit. All bedrooms and hallways have a battery operated smoke ( not interconnected ).
The ADA rooms have strobe/horns interconnected in each bed and hallway.
The lock on the SW exit from pool area is now a thumb turn bolt and there is a mesh wire screen around the lock to prevent little arms from reaching through the bars and accessing the lock.
The old 911 phone has been removed.
Emergency lights in the community room are operating correctly. Fire extinguisher in community room is provided.
07/20/2015 FIRE - FINAL Denied IFC 906.9 Add fire extinguishers on 2nd level of apartments, fire extinguishers 40 pounds or less shall be mounted max 5 feet above floor finish to top of extinguisher handle or min 4" fire extinguishers over 40 pounds mounted max 3.5 feet above floor finish min 4". Size of extinguisher shall be min 2A-10BC type