Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T14CM00781
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/13/2015 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/12/2015 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 05/06/2015 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/06/2015 | ELECTRIC - FINAL | Denied | 1. GROUNDING ELECTRODE MISSING BOND BUSHING 2. DISCONNECTS MISSING BONDING SCREW 3. DISCONNECT PAINT TO BE REMOVED UNDERGROUND LUG 4. BOND BUSHINGS MISSING ON NIPPLE 5. J-BOX MISSING PLASTIC BUSH AND BONDING |