Permit: T14CM00606

Parcel: 141096230

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
03/31/2014 BUILDING - FINAL Approved IVRS - Inspection :*
03/24/2014 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/24/2014 BUILDING - FINAL Denied 1. GROUNDING FROM SERVICE TO INVERTERS TO BE #8
2. WIRES ON ROOF TOUCHING, TIE THEM UP
3. PAPERWORK TO SHOW TWO INVERTERS
4. PV BREAKER TO BE 35 AMPS