Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T14CM00606
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/31/2014 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
03/24/2014 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
03/24/2014 | BUILDING - FINAL | Denied | 1. GROUNDING FROM SERVICE TO INVERTERS TO BE #8 2. WIRES ON ROOF TOUCHING, TIE THEM UP 3. PAPERWORK TO SHOW TWO INVERTERS 4. PV BREAKER TO BE 35 AMPS |