Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/05/2014 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/31/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/31/2014 | ELECTRIC - FINAL | Denied | MAX 20 AMP BREAKER ON #12 WIRE. GFCI RECEPTACLES REQUIRED IN SHED/GARAGE. NO CORD CONNECTING DEVICES "PERMANENT." LOWER FUSE SIZE TO SHED "APPEARS TO BE 60 AMP PANEL." EACH BUILDING REQ'S GROUNDING ELECTRODE SYSTEM AND DISCONNECT. ISOLATE NEUTRAL FROM EQUIPMENT GROUNDING CONDUCTORS AT SUBPANELS. VERIFY CABLE IS SUITED FOR DIRECT BURIAL AND AT CORRECT DEPTH. INCOMPLETE INSPECTION | |
| 02/07/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/07/2014 | ELECTRIC - FINAL | Denied | FAIL - INCOMPLETE INSPECTION. NUMBER 12 WIRE ILLEGALLY TOPPED-OFF, 200 AMP FUSES. PANEL AND PAPERWORK ADDRESSING DO NOT MATCH. 100 AMP BREAKER NOT MOUNTED CORRECTLY IN PANEL. PANEL NEEDS KNOCK-OUT ON TOPSIDE. HAVE QUALIFIED ELECTRICIAN SIGNAL TRACE ALL CIRCUITS AND CHECK THOROUGHLY. |