03/12/2015 FIRE - FINAL Approved
12/24/2014 FIRE - FINAL Partial Approval Tested the emergency lighting by turning off the main breakers from TEP so as to use the emergency generator power only for all emergency lighting, walked the building found that lighting was very well no problem for exiting out of the building. Found problem on the eastside outside walkway no lighting came on had the electrician check the wiring and found it dead city of Tucson facilities will need to find were the wiring was disconnected from the generator system.
North exhibit hall emergency lighting passed and all exit signs passed.
10/06/2014 FIRE - FINAL Partial Approval Temp C of O approved for the use of the Arena only to get finals the following will need to be completed:
When testing the emergency generator by shutting down the power to the TCC no back up egress lighting came on in the following areas:
1. Outside egress lighting on the eastside upper level
2. Lower level southeast exit stair well
3. North exhibit hall no lighting at all and two of the three exit signs failed over doors with three
4. Need to finsh lower level coverage when clouds are install and need as bults for piping changes. (PG. 2 of approved plans)