Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/03/2014 | ELECTRIC - FINAL | Denied | 1. PROVIDE #8 TO C.U ON ROOF 2. SEAL ROOF PENETRATIONS 3. CONDENSATE NOT PROPERLY TERMINATED 4. PROVIDE B VENT AT WATER HEATER 5. PROVIDE SECONDARY DRAIN 6. GAS FLEX NOT TO PENETRATE CABINET |
|
| 01/27/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/27/2014 | ELECTRIC - FINAL | Denied | 1. BUSS BARS ARE BURNT AND NEED TO BE REPLACED 2. A/C POWER INSTALLED WITHOUT PERMIT, PROVIDE APPROVED HUB FITTINGS IF ENTERING TOP OF PANEL, CONDUIT NOT PROPERLY ATTACHED TO WALL 3. PLUG KO AT BOTTOM OF PANEL |