Permit: T14CM00358

Parcel: 120084150

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/01/2015 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/21/2015 ELECTRIC - FINAL Not ready for Inspection wall heaters not wired or installed
04/08/2015 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
04/08/2015 ELECTRIC - FINAL Partial Approval ITEM #4 DATED 01/29/14 NOT CORRECTED. WORK IN 2ND HOUSE IS COMPLETED AND COVERED UP. PROVIDE ACCESS FOR INSPECTION
01/29/2014 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/29/2014 ELECTRIC - FINAL Denied 1. PLUG HOLE IN BACK OF SUBPANEL, BUSHING REQUIRED ON PVC MALE ADAPTORS, BOTH PANELS
2. LB COVER CANNOT BE IN GROUND, SUPPORT CONDUIT, ALSO A TRIP HAZARD
3. GROUNDING ELECTRODE SYSTEM AT 2ND HOUSE
4. OBTAIN PLAN/PERMIT FOR WIRING OF 2ND HOUSE
5. SPLIT BOLT NOT APPROVED FOR SPLICING GROUND ELECTRODE CONDUCTOR AT MAIN SERVICE
6. HOMEMADE RISER CONDUIT BRACE NOT APPROVED, USE A LISTED BRACE
7. USE SAME CIRCUIT BREAKERS AS PANEL MANUF (BRAND)
8. SUPPORT RECEPT BOXES
9. 100 AMP CKT BRKR FOR #2 CU FEEDER
10. GROUND RODS TO BE FLUSH WITH GRADE (TRIP HAZARD)