Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/01/2015 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/21/2015 | ELECTRIC - FINAL | Not ready for Inspection | wall heaters not wired or installed | |
| 04/08/2015 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 04/08/2015 | ELECTRIC - FINAL | Partial Approval | ITEM #4 DATED 01/29/14 NOT CORRECTED. WORK IN 2ND HOUSE IS COMPLETED AND COVERED UP. PROVIDE ACCESS FOR INSPECTION | |
| 01/29/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/29/2014 | ELECTRIC - FINAL | Denied | 1. PLUG HOLE IN BACK OF SUBPANEL, BUSHING REQUIRED ON PVC MALE ADAPTORS, BOTH PANELS 2. LB COVER CANNOT BE IN GROUND, SUPPORT CONDUIT, ALSO A TRIP HAZARD 3. GROUNDING ELECTRODE SYSTEM AT 2ND HOUSE 4. OBTAIN PLAN/PERMIT FOR WIRING OF 2ND HOUSE 5. SPLIT BOLT NOT APPROVED FOR SPLICING GROUND ELECTRODE CONDUCTOR AT MAIN SERVICE 6. HOMEMADE RISER CONDUIT BRACE NOT APPROVED, USE A LISTED BRACE 7. USE SAME CIRCUIT BREAKERS AS PANEL MANUF (BRAND) 8. SUPPORT RECEPT BOXES 9. 100 AMP CKT BRKR FOR #2 CU FEEDER 10. GROUND RODS TO BE FLUSH WITH GRADE (TRIP HAZARD) |