Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2014 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/03/2014 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 06/03/2014 | ELECTRIC - FINAL | Partial Approval | FA LEFT TO INSPECT FOR FINAL | |
| 03/27/2014 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 02/20/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/20/2014 | ELECTRIC - FINAL | Denied | 1. NO MAIN SERVICE DISCONNECT SWITCH AT SERVICE 2. COULD NOT VERIFY SERVICE GROUND 3. CEILING FANS NOT WIRED TO CODE 4. FA SYSTEM HAS BEEN VANDALIZED 5. MISSING WATER HTR'S OR NOT CONNECTED |