Permit: T14CM00168

Parcel: 130050420


Addresses:

1929 S CAMPBELL AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/01/2014 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/31/2014 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/31/2014 ELECTRIC - FINAL Denied CABLE OUTER COVERING MUST BE AT LEAST 1/4" INSIDE PANEL ENCLOSURE. SEAL PENETRATIONS IN BACK WITH NON-COMBUSTIBLE SEALANT.
03/31/2014 ELECTRIC - FINAL Denied GROUNDING SYSTEMS, BOTH SERVICES TO BE COMMON. CIRCUIT BREAKER FOR H20 HEATER SHOULD BE 30 AMP
03/27/2014 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/13/2014 ELECTRIC - FINAL Denied -NO GROUNDING SYSTEM OVER SIZED CKT BREAKERS FOR WIRING OF BRANCH CIRCUITS
- UPGRADE TO 200 AMPS OR 100 AMPS MUST INCLUDE
-COMPLETE SYSTEM METER RISER WIRING
-SUPPORT CONDUITS PER CODE
-RISER WEATHER HEAD TO LOW SERVICE CONDUCTORS LAYING ON ROOF PROVIDE ADDRESS LABELS USE A LICENSED ELECTRICIAN TO DO WORK
- MUST HAVE BUSHINGS TO PROTECT WIRING INTO ENCLOSURE CABLES TO BE TERMINATED WITH APPROVED CONNECTORS AND 1/4" OF CABLE SHEATH INTO ENCLOSURE
01/10/2014 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*