Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2014 | ELECTRIC - FINAL | Approved | ||
| 02/12/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/12/2014 | ELECTRIC - FINAL | Denied | THE WELD ON THE LOWER SECTION IS POOR QUALITY & IS BROKEN | |
| 02/06/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/06/2014 | ELECTRIC - FINAL | Denied | THE SPLICING USED FOR THE GROUNDING ELECTRODE CONDUCTOR NOT ALLOWED. YOU MUST USE AN IRREVERSIBLE SPLICE. EITHER CAD WELD CONDUCTORS OR USE A CRIMP TYPE SPLICE. | |
| 01/13/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/13/2014 | ELECTRIC - FINAL | Denied | 1. PERMANENT LABEL SERVICE DISCONNECT 2. PANEL NOT GROUNDED - GROUND WIRE CUT 3. INTERIOR OK |