Permit: T14CM00167

Parcel: 125123170


Addresses:

969 N JONES BL #08

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/14/2014 ELECTRIC - FINAL Approved
02/12/2014 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/12/2014 ELECTRIC - FINAL Denied THE WELD ON THE LOWER SECTION IS POOR QUALITY & IS BROKEN
02/06/2014 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/06/2014 ELECTRIC - FINAL Denied THE SPLICING USED FOR THE GROUNDING ELECTRODE CONDUCTOR NOT ALLOWED. YOU MUST USE AN IRREVERSIBLE SPLICE. EITHER CAD WELD CONDUCTORS OR USE A CRIMP TYPE SPLICE.
01/13/2014 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/13/2014 ELECTRIC - FINAL Denied 1. PERMANENT LABEL SERVICE DISCONNECT
2. PANEL NOT GROUNDED - GROUND WIRE CUT
3. INTERIOR OK