Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/28/2014 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 05/22/2014 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/22/2014 | BUILDING - FINAL | Denied | SEE NOTES LAST INPSECTION - A RE-INSPECTION FEE WILL BE ASSESSED NEXT INSPECTION IF NO COMPLIANCE | |
| 05/20/2014 | BUILDING - FINAL | Denied | - PROVIDE APPROVED PLANS AND PERMIT - LADDER LONG ENOUGH TO PROVIDE 3' ABOVE ROOF PARAPIT REFEE CUSTOMER |
|
| 05/20/2014 | BUILDING - FINAL | Denied | **NO MESSAGE - 8AM** - 3RD ATTEMPT TO MAKE INSPECTION - NO COMPLIANCE W/ PREVIOUS INSPECTION NOTES - A RE-INSPECTION FEE IS ASSESSED, PAY RE-FEE AT 201 N STONE PRIOR TO NEXT INSPECTION |
|
| 05/16/2014 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/16/2014 | BUILDING - FINAL | Denied | - SEE NOTES LAST INSPECTION, APPROVED PLANS?? LADDER?? - CANNOT USE 70 AMP CIRCUIT BREAKER, EXCEEDS 125% OF PANEL BUSS RATING - 690 NEC |
|
| 05/15/2014 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/15/2014 | BUILDING - FINAL | Denied | - PROVIDE APPROVED PLANS - LADDER LONG ENOUGH TO PROVIDE 3' ABOVE ROOF PARAPIT |